2012年9月の”2012 International Conference on Condition Monitoring and Diagnosis”にて以下の発表を行いました。
タイトル:
「New Diagnosis Method of Aging Degradation for Insulating Paper in Power Transformers by Measuring the Refractive Index of Cellulose Fibers」
著者:
吉田昌展, 内田克己(中部電力)
小西義則, 加藤雅道(ユカインダストリーズ)
DOI:
https://doi.org/10.1109/CMD.2012.6416188
abstract
This paper proposes a new diagnosis method for aging degradation of insulating paper in power transformers. We took notice of cellulose fibers that suspended in insulating oil in transformers as useful samples for estimating degradation of insulating paper in transformers. The Mahalanobis-Taguchi System was applied for investigating the relationship between degradation and refractive indices of cellulose fibers measured.
It was found that aging degradation of cellulose fibers on insulating paper accompanies a change of dispersion color. This result shows that it is capable to estimate degradation of the paper in oil-immersed power transformers by measuring dispersion color of fibers suspended in insulating oil.
詳しい内容については、当社営業部までお問合せください。
お問い合わせ
ユカインダストリーズへのお問い合わせ・資料請求のご依頼は、お電話もしくはメールフォームより承っております。 お気軽にお問い合わせください。
お問い合わせ受付時間:8:30~17:30 定休日:土・日・祝日